600/1000V XLPE Insulated, PVC Sheathed, Double steel tape armoured Power Cables (2 Cores)
FGD400 1RVF2V-R (CU/XLPE/DSTA/PVC 600/1000V Class 2)
APPLICATION
The cables are mainly used in power stations, mass transit underground passenger systems,airports,petrochemical plants,hotels, hospitals, and high-rise buildings
STANDARDS
- Basic design adapted to IEC 60502-1
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test)** |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)** |
EN 60332-3-22 (cat. A); IEC 60332-3-22; BS EN 60332-3-22; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.
VOLTAGE RATING
600/1000 V
CABLE CONSTRUCTION
Conductor |
Plain annealed copper wire, normal stranded or compact stranded according to IEC 60228 class 2 |
Insulation |
Extruded XLPE compound |
Filler, binder(if any) |
PP,PET |
Inner Sheath(optional) |
Thermoplastic PVC compound |
Armouring |
Double steel tape armouring |
Outer Sheath |
Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance,anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request |
COLOUR CODE
Insulation Colour as per BS7671
|
With Earth Conductor |
Without Earth Conductor |
2Cores |
- |
Brown, Blue |
3Cores |
Yellow/Green, Brown, Blue |
Brown, Gray, Black |
4Cores |
Yellow/Green, Brown, Gray, Black |
Brown, Gray, Black, Blue |
5Cores |
Yellow/Green, Brown, Gray, Black, Blue |
Brown, Gray, Black, Blue, Black |
Above 5 Cores |
Yellow/Green, Black Numbered |
Black Numbered |
Sheath Colour: Black (other colors upon request)
PHYSICAL AND THERMAL PROPERTIES
Maximum temperature range during operation (XLPE) |
90°C |
Maximum short circuit temperature (5 Seconds) |
250°C |
Minimum bending radius |
10 x Overall Diameter |
CONSTRUCTION PARAMETERS
Conductor |
FGD400 1RVF2V-R |
No. of Core X
Cross Section |
No./Nominal Diameter of Strands |
Diameter Overall Conducrtor |
Nominal Insulation Thickness |
Steel
Tape
Thickness |
Nominal Sheath Thickness |
Nominal Overall Diatemer |
Max.DC resistance
of conductor @20°C |
Approx.
Weight |
mm2 |
No/mm |
mm |
mm |
mm |
mm |
mm |
Ω/km |
Kg/km |
2x6 |
7/1.04 |
2.90 |
0.7 |
0.2 |
1.8 |
16.8 |
3.08 |
417 |
2x10 |
7/1.35 |
3.75 |
0.7 |
0.2 |
1.8 |
18.5 |
1.83 |
539 |
2x16 |
7/1.70 |
4.75 |
0.7 |
0.2 |
1.8 |
20.5 |
1.15 |
704 |
2x25 |
7/2.14 |
5.85 |
0.9 |
0.2 |
1.8 |
23.5 |
0.727 |
971 |
2x35 |
7/2.52 |
6.90 |
0.9 |
0.2 |
1.8 |
25.6 |
0.524 |
1,216 |
2x5O |
19/1.78 |
8.15 |
1.0 |
0.2 |
1.8 |
28.5 |
0.387 |
1,582 |
2x70 |
19/2.14 |
9.75 |
1.1 |
0.2 |
1.9 |
32.3 |
0.268 |
2081 |
2x95 |
19/2.52 |
11.45 |
1.1 |
0.2 |
2.0 |
36.4 |
0.193 |
2749 |
2x120 |
37/2.03 |
12.85 |
1.2 |
0.5 |
2.2 |
41.1 |
0.153 |
3,727 |
2x150 |
37/2.25 |
14.30 |
1.4 |
0.5 |
2.3 |
45.1 |
0.124 |
4,509 |
2x185 |
37/2.52 |
15.95 |
1.6 |
0.5 |
2.5 |
49.9 |
0.0991 |
5,523 |
2x240 |
61/2.25 |
18.25 |
1.7 |
0.5 |
2.6 |
55.3 |
0.0754 |
6981 |
2x300 |
61/2.52 |
20.40 |
1.8 |
0.5 |
2.8 |
60.7 |
0.0601 |
8,383 |
2x400 |
61/2.85 |
23.35 |
2.0 |
0.5 |
3.0 |
67.9 |
0.0470 |
10,897 |
ELECTRICAL PROPERTIES
Conductor Operating Temperature |
90°C |
Ambient Temperature |
30°C |
Current-Carrying Capacities (Amp)
Conductor cross-sectional area |
Reference Method C (clipped direct) |
Reference Method E (in free air or on a perforated cable tray, horizontal or vertical) |
Reference Method D (direct in in groud or in ducting in groud.in or around buildings) |
1 two-core cable*, single-phase a.c. or d.c. |
1 three-or four core cable*,three-phase a.c. |
1 two-core cable*, single-phasea.c. or d.c. |
1 three-or four core cable*,three-phase a.c. |
1 two-core cable*, single-phase a.c. or d.c. |
1 three-or fourcore cable*, three-phase a.c. |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
mm2 |
A |
A |
A |
A |
A |
A |
6 |
62 |
53 |
66 |
56 |
53 |
44 |
10 |
85 |
73 |
90 |
78 |
71 |
58 |
16 |
110 |
94 |
115 |
99 |
91 |
75 |
25 |
146 |
124 |
152 |
131 |
116 |
96 |
35 |
180 |
154 |
188 |
162 |
139 |
115 |
50 |
219 |
187 |
228 |
197 |
164 |
135 |
70 |
279 |
238 |
291 |
251 |
203 |
167 |
95 |
338 |
289 |
354 |
304 |
239 |
197 |
120 |
392 |
335 |
410 |
353 |
271 |
223 |
150 |
451 |
386 |
472 |
406 |
306 |
251 |
185 |
515 |
441 |
539 |
463 |
343 |
281 |
240 |
607 |
520 |
636 |
546 |
395 |
324 |
300 |
698 |
599 |
732 |
628 |
446 |
365 |
400 |
787 |
673 |
847 |
728 |
- |
- |
Voltage Drop (Per Amp Per Meter)
Conductor cross-sectional area |
Two-core cables, d.c. |
Two-core cable, single-phase a.c. |
Three-or four core cable, three-phase a.c. |
1 |
2 |
3 |
4 |
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
6 |
7.9 |
7.9 |
6.8 |
10 |
4.7 |
4.7 |
4.0 |
16 |
2.9 |
2.9 |
2.5 |
|
|
r |
x |
z |
r |
x |
z |
25 |
1.85 |
1.85 |
0.160 |
1.90 |
1.60 |
0.140 |
1.65 |
35 |
1.35 |
1.35 |
0.155 |
1.35 |
1.15 |
0.135 |
1.15 |
50 |
0.98 |
0.99 |
0.155 |
1.00 |
0.86 |
0.135 |
0.87 |
70 |
0.67 |
0.67 |
0.150 |
0.69 |
0.59 |
0.130 |
0.60 |
95 |
0.49 |
0.50 |
0.150 |
0.52 |
0.43 |
0.130 |
0.45 |
120 |
0.39 |
0.40 |
0.145 |
0.42 |
0.34 |
0.130 |
0.37 |
150 |
0.31 |
0.32 |
0.145 |
0.35 |
0.38 |
0.125 |
0.30 |
185 |
0.25 |
0.26 |
0.145 |
0.29 |
0.22 |
0.125 |
0.26 |
240 |
0.195 |
0.200 |
0.140 |
0.24 |
0.175 |
0.125 |
0.21 |
300 |
0.155 |
0.160 |
0.140 |
0.21 |
0.140 |
0.120 |
0.185 |
400 |
0.120 |
0.130 |
0.140 |
0.190 |
0.115 |
0.120 |
0.165 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance