600/1000V XLPE Insulated, LSZH Sheathed, Armoured Power Cables to IEC60502-1 (Single Core)
FTX300 1RZ1MAZ1-R (CU/XLPE/LSZH/AWA/LSZH 600/1000V Class 2)
APPLICATION
This cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.
STANDARDS
- Basic design adapted to IEC 60502-1
FIRE PERFORMANC
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free |
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1; BS 6425-1* |
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases |
NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
600/1000 V
CABLE CONSTRUCTIO
Conductor |
Plain annealed copper wire, stranded according to IEC 60228 class 2 |
Insulation |
Extruded XLPE compound |
Inner Sheath(optional) |
Thermoplastic LSZH compound |
Armouring |
Aluminium wire |
Outer Sheath |
Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option |
COLOUR CODE
Insulation Colour as per BS7671 |
|
Sheath Colour |
Black (other colors upon request) |
PHYSICAL AND THERMAL PROPERTIES
Maximum temperature range during operation (XLPE) |
90°C |
Maximum short circuit temperature (5 Seconds) |
250°C |
Minimum bending radius |
10 x Overall Diameter |
CONSTRUCTION PARAMETERS
Conductor |
FTX300 1RZ1MAZ1-R |
No. of Core X Cross Section |
No./Nominal Diameter of Strands |
Nominal Insulation Thickness |
Diameter Under Armour |
Armour Wire Diameter |
Nominal Overall Diameter |
Approx. Weight |
mm2 |
No./mm |
mm |
mm |
mm |
mm |
kg/km |
1x70 |
19/2.14 |
1.1 |
15.4 |
1.25 |
21.5 |
960 |
1x95 |
19/2.52 |
1.1 |
17.3 |
1.25 |
23.4 |
1240 |
1x120 |
37/2.03 |
1.2 |
19.1 |
1.6 |
25.9 |
1650 |
1x150 |
37/2.25 |
1.4 |
21.1 |
1.6 |
27.9 |
1970 |
1x185 |
37/2.52 |
1.6 |
23.2 |
1.6 |
30.1 |
2390 |
1x240 |
61/2.25 |
1.7 |
26.2 |
1.6 |
33.2 |
3040 |
1x300 |
61/2.52 |
1.8 |
28.8 |
1.6 |
35.8 |
3790 |
1x400 |
61/2.85 |
2.0 |
32.7 |
2.0 |
40.9 |
4790 |
1x500 |
61/3.20 |
2.2 |
36.2 |
2.0 |
44.6 |
5880 |
1x630 |
127/2.52 |
2.4 |
40.6 |
2.0 |
49.2 |
7400 |
1x800 |
127/2.85 |
2.6 |
45.7 |
2.5 |
55.7 |
9500 |
1x1000 |
127/3.20 |
2.8 |
50.6 |
2.5 |
61.0 |
11750 |
ELECTRICAL PROPERTIES
Conductor Operating Temperature |
90°C |
Ambient Temperature |
30°C |
Current-Carrying Capacities (Amp)
Conductor cross-sectional area |
Reference Method C (clipped direct) |
Reference Method F (in free air or on a perforated cable tray, horizontal or vertical) |
|
Touching |
|
Touching |
Spaced by on cable diameter |
|
2 cables, single-phase a.c. or d.c. flat |
3 or 4 cables, three-phase a.c. flat |
2 cables, single-phase a.c. or d.c. flat |
3 or 4 cables, three-phase a.c. flat |
3 cables three-phase a.c. trefoil |
2 cables, d.c. |
2 cables, single-phase a.c. |
3 or 4 cables,three-phase a.c. |
Horizontal |
Vertical |
Horizontal |
Vertical |
Horizontal |
Vertical |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
70 |
303 |
277 |
322 |
293 |
285 |
356 |
349 |
357 |
337 |
358 |
331 |
95 |
367 |
333 |
389 |
352 |
346 |
446 |
426 |
436 |
412 |
425 |
393 |
120 |
425 |
383 |
449 |
405 |
402 |
519 |
497 |
504 |
477 |
485 |
449 |
150 |
488 |
437 |
516 |
462 |
463 |
600 |
575 |
566 |
539 |
549 |
510 |
185 |
557 |
496 |
587 |
524 |
529 |
688 |
660 |
643 |
614 |
618 |
574 |
240 |
656 |
579 |
689 |
612 |
625 |
815 |
782 |
749 |
714 |
715 |
666 |
300 |
755 |
662 |
792 |
700 |
720 |
943 |
906 |
842 |
805 |
810 |
755 |
400 |
853 |
717 |
899 |
767 |
815 |
1137 |
1094 |
929 |
889 |
848 |
797 |
500 |
962 |
791 |
1016 |
851 |
918 |
1314 |
1266 |
1032 |
989 |
923 |
871 |
630 |
1082 |
861 |
1146 |
935 |
1027 |
1528 |
1474 |
1139 |
1092 |
992 |
940 |
800 |
1170 |
904 |
1246 |
987 |
1119 |
1809 |
1744 |
1204 |
1155 |
1042 |
978 |
1000 |
1261 |
961 |
1345 |
1055 |
1214 |
2100 |
2026 |
1289 |
1238 |
1110 |
1041 |
Voltage Drop (Per Amp Per Meter)
Nominal Cross Section Area 1 |
2 cables d.c.2 |
Ref. Methods C&F(clipped direct, on trays or in free air) |
2 cables, single-phase a.c. |
3 or 4 cables, three-phase a.c. |
Touching 3 |
Spaced*4 |
Trefoil and touching 5 |
Flat and touching 6 |
Flat and spaced*7 |
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
|
|
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
70 |
0.67 |
0.68 |
0.20 |
0.71 |
0.69 |
0.29 |
0.75 |
0.59 |
0.170 |
0.62 |
0.60 |
0.25 |
0.65 |
0.62 |
0.32 |
0.70 |
95 |
0.49 |
0.51 |
0.195 |
0.55 |
0.53 |
0.28 |
0.60 |
0.44 |
0.170 |
0.47 |
0.46 |
0.24 |
0.52 |
0.49 |
0.31 |
0.58 |
120 |
0.39 |
0.41 |
0.190 |
0.45 |
0.43 |
0.27 |
0.51 |
0.35 |
0.165 |
0.39 |
0.38 |
0.34 |
0.44 |
0.41 |
0.30 |
0.51 |
150 |
0.31 |
0.33 |
0.185 |
0.38 |
0.36 |
0.27 |
0.45 |
0.29 |
0.160 |
0.33 |
0.31 |
0.23 |
0.39 |
0.34 |
0.39 |
0.45 |
185 |
0.25 |
0.27 |
0.185 |
0.33 |
0.30 |
0.26 |
0.40 |
0.23 |
0.160 |
0.28 |
0.26 |
0.23 |
0.34 |
0.29 |
0.29 |
0.41 |
240 |
0.195 |
0.21 |
0.180 |
0.28 |
0.24 |
0.26 |
0.35 |
0.180 |
0.155 |
0.24 |
0.21 |
0.22 |
0.30 |
0.24 |
0.28 |
0.37 |
300 |
0.155 |
0.17 |
0.175 |
0.25 |
0.195 |
0.25 |
0.32 |
0.145 |
0.150 |
0.21 |
0.170 |
0.22 |
0.28 |
0.20 |
0.27 |
0.34 |
400 |
0.115 |
0.145 |
0.170 |
0.22 |
0.180 |
0.24 |
0.30 |
0.125 |
0.150 |
0.195 |
0.160 |
0.21 |
0.27 |
0.20 |
0.27 |
0.33 |
500 |
0.093 |
0.125 |
0.170 |
0.21 |
0.165 |
0.24 |
0.29 |
0.105 |
0.145 |
0.180 |
0.145 |
0.20 |
0.25 |
0.190 |
0.24 |
0.31 |
630 |
0.073 |
0.105 |
0.165 |
0.195 |
0.150 |
0.23 |
0.27 |
0.092 |
0.145 |
0.170 |
0.135 |
0.195 |
0.24 |
0.175 |
0.23 |
0.29 |
800 |
0.056 |
0.090 |
0.160 |
0.190 |
0.145 |
0.23 |
0.27 |
0.086 |
0.140 |
0.165 |
0.130 |
0.180 |
0.23 |
0.175 |
0.195 |
0.26 |
1000 |
0.045 |
0.092 |
0.155 |
0.180 |
0.140 |
0.21 |
0.25 |
0.080 |
0.135 |
0.155 |
0.125 |
0.170 |
0.21 |
0.165 |
0.180 |
0.24 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance