VFD-Shielded Power Cable
Application
These high performance VFD cables are for dynamic industrial applications that reduces the effects of electrical noise and corona discharge, while providing a low impedance path to ground to eliminate the potential damage.
Construction
| Conductor | Stranded fine copper conductor. |
| Insulation | Oil resistant composite material, provide high dielectric, tensile and mechanical properties. |
| Color code | 3 black cores+1 yellow/green. |
| Filers | Low friction, non-wicking fillers provide increased flexibility in dynamic applications. |
| Drain wire | Flat braid drain wire. |
| Braid | 100% coverage tinned copper braid. |
| Sheath | Special TPE compound, oil, ozone, UV resistant, flame and heat resistant. All-weather flexibility. |
Technical Information
| CSA – 1000 Volt |
| CSA – FT-4 |
| TC-ER – 600 Volt |
| Rated temperature – 90C |
Cable Parameter
| No. Of Cores | Cable Size | Stranding | Ampacity | Nominal | WT. (LBS.) | Drain Wire |
|---|---|---|---|---|---|---|
| AWG | (1) | O.D. (IN.) | PER 1000' | AWG | ||
| 4 | 16 | 65 x 34 | 18 | 0.465 | 145 | 18 |
| 4 | 14 | 105 x 34 | 25 | 0.509 | 158 | 16 |
| 4 | 12 | 165 x 34 | 30 | 0.606 | 247 | 14 |
| 4 | 10 | 105 x 30 | 40 | 0.683 | 308 | 14 |
| 4 | 8 | 168 x 30 | 55 | 0.887 | 528 | 14 |
| 4 | 6 | 266 x 30 | 75 | 1.020 | 753 | 14 |
| 4 | 4 | 413 x 30 | 95 | 1.190 | 1083 | 14 |