600/1000V XLPE Insulated, PVC Sheathed, Armoured Power Cables (Single Core) to BS 5467

FGD300 1RVMAV-R (CU/XLPE/PVC/AWA/PVC 600/1000V Class 2)

APPLICATION

The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.

images/600-1000V XLPE Insulated, PVC Sheathed, Armoured Power Cables (Single Core).jpg images/600-1000V PVC Sheathed, Armoured Power Cables.jpg

STANDARDS

  • Basic design adapted to IEC 60502-1

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)** EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)** EN 60332-3-22 (cat. A); IEC 60332-3-22; BS EN 60332-3-22; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

VOLTAGE RATING

600/1000 V

CABLE CONSTRUCTION

Conductor Plain annealed copper wire, stranded according to IEC 60228 class 2
Insulation Extruded XLPE compound
Inner Sheath(optional) Thermoplastic PVC compound
Armouring Aluminium Wire
Outer Sheath Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request

COLOUR CODE

Insulation Colour as per BS7671  
Sheath Colour Black (other colors upon request)

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation (XLPE) 90°C
Maximum short circuit temperature (5 Seconds) 250°C
Minimum bending radius 10 x Overall Diameter

CONSTRUCTION PARAMETERS

No. of Core X Cross Section No./Nominal Diameter of Strands Nominal Insulation Thickness Nominal Bedding Thickness Nominal Alum Wire Diameter Nominal Sheath Thickness Approx. Overall Diameter Aprrox Weight
No.×mm^2 No./mm mm mm mm mm mm kg/km
1x50 19/1.78 1.0 0.8 0.9 1.5 17.5 800
1x70 19/2.14 1.1 0.8 1.25 1.5 20.2 990
1x95 19/2.52 1.1 0.8 1.25 1.6 22.3 1280
1x120 37/2.03 1.2 0.8 1.25 1.6 24.2 1550
1x150 37/2.25 1.4 1.0 1.6 1.7 27.4 1900
1x185 37/2.52 1.6 1.0 1.6 1.8 30.0 2320
1x240 61/2.25 1.7 1.0 1.6 1.8 32.8 2930
1x300 61/2.52 1.8 1.0 1.6 1.9 35.6 3580
1x400 61/2.85 2.0 1.2 2.0 2.0 40.5 4600
1x500 61/3.20 2.2 1.2 2.0 2.1 44.2 5680
1x630 127/2.52 2.4 1.2 2.0 2.2 48.8 7160
1x800 127/2.85 2.6 1.4 2.5 2.4 55.4 9315
1x1000 127/3.20 2.8 1.4 2.5 2.5 60.6 11490

ELECTRICAL PROPERTIES

Conductor Operating Temperature 70°C
Ambient Temperature 30°C

Current-Carrying Capacities (Amp)

Conductor cross-sectional area Reference Method C (clipped direct) Reference Method F (in free air or on a perforated cable tray, horizontal or vertical)
  Touching Touching Spaced by on cable diameter
2 cables, single-phase a.c. or d.c. flat 3 or 4 cables,three-phase a.c. flat 2 cables, single-phase a.c. or d.c. flat 3 or 4 cables, three-phase a.c. flat 3 cables three-phase a.c. trefoil 2 cables, d.c. 2 cables, single-phase a.c. 3 or 4 cables,three-phase a.c.
Horizontal Vertical Horizontal Vertical Horizontal Vertical
1 2 3 4 5 6 7 8 9 10 11 12
mm2 A A A A A A A A A A A
70 303 277 322 293 285 356 349 357 337 358 331
95 367 333 389 352 346 446 426 436 412 425 393
120 425 383 449 405 402 519 497 504 477 485 449
150 488 437 516 462 463 600 575 566 539 549 510
185 557 496 587 524 529 688 660 643 614 618 574
240 656 579 689 612 625 815 782 749 714 715 666
300 755 662 792 700 720 943 906 842 805 810 755
400 853 717 899 767 815 1137 1094 929 889 848 797
500 962 791 1016 851 918 1314 1266 1032 989 923 871
630 1082 861 1146 935 1027 1528 1474 1139 1092 992 940
800 1170 904 1246 987 1119 1809 1744 1204 1155 1042 978
1000 1261 961 1345 1055 1214 2100 2026 1289 1238 1110 1041

Voltage Drop (Per Amp Per Meter)

Nominal Cross Section Area 1 2 cables d.c. 2 Ref. Methods C&F(clipped direct, on trays or in free air)
2 cables, single-phase a.c. 3 or 4 cables, three-phase a.c.
Touching 3 Spaced* 4 Trefoil and touching 5 Flat and touching 6 Flat and spaced*7
mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
r x z r x z r x z r x z r x z
70 0.67 0.68 0.20 0.71 0.69 0.29 0.75 0.59 0.170 0.62 0.60 0.25 0.65 0.62 0.32 0.70
95 0.49 0.51 0.195 0.55 0.53 0.28 0.60 0.44 0.170 0.47 0.46 0.24 0.52 0.49 0.31 0.58
120 0.39 0.41 0.190 0.45 0.43 0.27 0.51 0.35 0.165 0.39 0.38 0.34 0.44 0.41 0.30 0.51
150 0.31 0.33 0.185 0.38 0.36 0.27 0.45 0.29 0.160 0.33 0.31 0.23 0.39 0.34 0.39 0.45
185 0.25 0.27 0.185 0.33 0.30 0.26 0.40 0.23 0.160 0.28 0.26 0.23 0.34 0.29 0.29 0.41
240 0.195 0.21 0.180 0.28 0.24 0.26 0.35 0.180 0.155 0.24 0.21 0.22 0.30 0.24 0.28 0.37
300 0.155 0.17 0.175 0.25 0.195 0.25 0.32 0.145 0.150 0.21 0.170 0.22 0.28 0.20 0.27 0.34
400 0.115 0.145 0.170 0.22 0.180 0.24 0.30 0.125 0.150 0.195 0.160 0.21 0.27 0.20 0.27 0.33
500 0.093 0.125 0.170 0.21 0.165 0.24 0.29 0.105 0.145 0.180 0.145 0.20 0.25 0.190 0.24 0.31
630 0.073 0.105 0.165 0.195 0.150 0.23 0.27 0.092 0.145 0.170 0.135 0.195 0.24 0.175 0.23 0.29
800 0.056 0.090 0.160 0.190 0.145 0.23 0.27 0.086 0.140 0.165 0.130 0.180 0.23 0.175 0.195 0.26
1000 0.045 0.092 0.155 0.180 0.140 0.21 0.25 0.080 0.135 0.155 0.125 0.170 0.21 0.165 0.180 0.24

Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance