600/1000V XLPE Insulated, LSZH Sheathed, Screened Power Cables (4 Cores)
FTX400 1RZ1CZ1MZ1-R (CU/XLPE/LSZH/CUTO/LSZH/SWA/LSZH 600/1000V Class 2)
APPLICATION
This cable is designed specifically to suit the broad spectrum of requirements of Variable Speed Drives and also include features for reducing the transmission of electromagnetic interference.
This range of screened cables drastically reduce interferences from electrical noise, especially in Variable Speed Drive (VSD) applications and are manufactured with fixed conductors.With shield conductivity of 1/10th of phase conductor conductivity, this range of VSD cables effectively restrain radiated and conducted radio-frequency emissions.
STANDARDS
- Basic design adapted to IEC 60502-1
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free |
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1; BS 6425-1* |
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases |
NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
600/1000 V
CABLE CONSTRUCTION
Conductor |
Plain annealed copper wire, stranded according to IEC 60228 class 2 |
Insulation |
Extruded XLPE compound |
Inner Sheath 1(optional) |
Thermoplastic LSZH compound |
Screen |
Copper tape |
Inner Sheath2(optional) |
Thermoplastic LSZH compound |
Armouring |
Galvanised steel wire |
Outer Sheath |
Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option |
COLOUR CODE
Insulation Colour as per BS7671
|
With Earth Conductor |
Without Earth Conductor |
4 Cores |
Yellow/Green, Brown, Grey, Black |
Brown, Grey, Black, Blue |
Sheath Colour: Black (other colors upon request)
PHYSICAL AND THERMAL PROPERTIES
Maximum temperature range during operation (XLPE) |
90°C |
Maximum short circuit temperature(5 Seconds) |
250°C |
Minimum bending radius |
12 x Overall Diameter |
CONSTRUCTION PARAMETERS
Conductor |
FTX400 1RZ1CZ1MZ1-R |
No. of Core X Cross Section |
No./Nominal Diameter of Strands |
Nominal Insulation Thickness |
Nominal Sheath Thickness |
Diameter Under Screen |
Diameter Over Inner Sheath |
Armour
Wire Diameter |
Nominal Overall Diameter |
Approx. Weight |
mm2 |
No./mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/km |
4x1.5 |
7/0.53 |
0.7 |
1.8 |
9.7 |
12.1 |
13.9 |
17.7 |
640 |
4x2.5 |
7/0.67 |
0.7 |
1.8 |
10.7 |
13.1 |
14.9 |
18.7 |
730 |
4x4.0 |
7/0.85 |
0.7 |
1.8 |
12.0 |
14.4 |
16.2 |
20.0 |
870 |
4x6.0 |
7/1.04 |
0.7 |
1.8 |
13.4 |
15.8 |
18.3 |
22.1 |
1180 |
4x10 |
7/1.35 |
0.7 |
1.8 |
15.6 |
18.0 |
20.5 |
24.3 |
1490 |
4x16 |
7/1.70 |
0.7 |
1.8 |
18.1 |
20.5 |
23.7 |
27.5 |
2070 |
4x25 |
7/2.14 |
0.9 |
1.8 |
22.3 |
24.1 |
27.3 |
31.1 |
2790 |
4x35(S) |
7/2.52 |
0.9 |
1.8 |
25.0 |
26.8 |
30.0 |
33.8 |
2940 |
4x50(S) |
19/1.78 |
1.0 |
2.0 |
27.8 |
29.6 |
32.8 |
37.0 |
3500 |
4x70(S) |
19/2.14 |
1.1 |
2.2 |
31.6 |
33.4 |
37.4 |
42.0 |
5000 |
4x95(S) |
19/2.52 |
1.1 |
2.3 |
35.4 |
37.2 |
41.2 |
46.0 |
6300 |
4x120(S) |
37/2.03 |
1.2 |
2.5 |
39.0 |
40.8 |
45.8 |
51.0 |
8200 |
4x150(S) |
37/2.25 |
1.4 |
2.6 |
42.0 |
43.8 |
48.8 |
54.2 |
9600 |
4x185(S) |
37/2.52 |
1.6 |
2.8 |
47.8 |
49.6 |
54.6 |
60.4 |
11500 |
4x240(S) |
61/2.25 |
1.7 |
3.0 |
54.0 |
55.8 |
60.8 |
67.0 |
14400 |
4x300(S) |
61/2.52 |
1.8 |
3.0 |
58.0 |
59.8 |
64.8 |
71.4 |
17200 |
ELECTRICAL PROPERTIES
Conductor Operating Temperature |
90°C |
Ambient Temperature |
30°C |
Current-Carrying Capacities (Amp)
Conductor cross-sectional area |
Reference Method C (clipped direct) |
Reference Method E (in free air or on a perforated cable tray, horizontal or vertical) |
Reference Method D (direct in in groud or in ducting in groud.in or around buildings) |
1 two-core cable*, single-phase a.c. or d.c. |
1 three-or four core cable*,three-phase a.c. |
1 two-core cable*, single-phase a.c. or d.c. |
1 three-or four core cable*,three-phase a.c. |
1 two-core cable*, single-phase a.c. or d.c. |
1 three-or fourcore cable*,three-phase a.c. |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
mm2 |
A |
A |
A |
A |
A |
A |
1.5 |
27 |
23 |
29 |
25 |
25 |
21 |
2.5 |
36 |
31 |
39 |
33 |
33 |
28 |
4.0 |
49 |
42 |
52 |
44 |
43 |
36 |
6.0 |
62 |
53 |
66 |
56 |
53 |
44 |
10 |
85 |
73 |
90 |
78 |
71 |
58 |
16 |
110 |
94 |
115 |
99 |
91 |
75 |
25 |
146 |
124 |
152 |
131 |
116 |
96 |
35 |
180 |
154 |
188 |
162 |
139 |
115 |
50 |
219 |
187 |
228 |
197 |
164 |
135 |
70 |
279 |
238 |
291 |
251 |
203 |
167 |
95 |
338 |
289 |
354 |
304 |
239 |
197 |
120 |
392 |
335 |
410 |
353 |
271 |
223 |
150 |
451 |
386 |
472 |
406 |
306 |
251 |
185 |
515 |
441 |
539 |
463 |
343 |
281 |
240 |
607 |
520 |
636 |
546 |
395 |
324 |
300 |
698 |
599 |
732 |
628 |
446 |
365 |
Voltage Drop (Per Amp Per Meter)
Conductor cross-sectional area |
Two-core cables, d.c. |
Two-core cable, single-phase a.c. |
Three-or four core cable, three-phase a.c. |
1 |
2 |
3 |
4 |
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
1.5 |
31 |
31 |
27 |
2.5 |
19 |
19 |
16 |
4 |
12 |
12 |
10 |
6 |
7.9 |
7.9 |
6.8 |
10 |
4.7 |
4.7 |
4.0 |
16 |
2.9 |
2.9 |
2.5 |
|
|
r |
x |
z |
r |
x |
z |
25 |
1.85 |
1.85 |
0.160 |
1.90 |
1.60 |
0.140 |
1.65 |
35 |
1.35 |
1.35 |
0.155 |
1.35 |
1.15 |
0.135 |
1.15 |
50 |
0.98 |
0.99 |
0.155 |
1.00 |
0.86 |
0.135 |
0.87 |
70 |
0.67 |
0.67 |
0.150 |
0.69 |
0.59 |
0.130 |
0.60 |
95 |
0.49 |
0.50 |
0.150 |
0.52 |
0.43 |
0.130 |
0.45 |
120 |
0.39 |
0.40 |
0.145 |
0.42 |
0.34 |
0.130 |
0.37 |
150 |
0.31 |
0.32 |
0.145 |
0.35 |
0.38 |
0.125 |
0.30 |
185 |
0.25 |
0.26 |
0.145 |
0.29 |
0.22 |
0.125 |
0.26 |
240 |
0.195 |
0.200 |
0.140 |
0.24 |
0.175 |
0.125 |
0.21 |
300 |
0.155 |
0.160 |
0.140 |
0.21 |
0.140 |
0.120 |
0.185 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance