Reference notes
Notes
CCV, CCE, CEV, CEE and so on can be supplied upon request.
Product momenclature
| C | XLPE insulation |
| V | PVC insulation / sheath |
| E | PE insulation / sheath |
| S | Copper tape shield |
| SB | Copper braid shield |
| SWA | Galvanized steel wire armour |
| F | Flat cable |
| R | Round cable |
Insulation and sheath options
Insulation options
PVC,(flame retardant PVC and heat resistant PVC can also be supplied upon request) / XLPE / PE
Sheath options
PVC,(flame retardant PVC and heat resistant PVC can also be supplied upon request) / PE
Characteristics
| XLPE | Tensile strength, min | 12.5N/mm^2 (1.27kg/mm^2) |
| Elongation at break, min | 200% | |
| After aging Requirement(Treatment : Temperature135±3°C, Duration 7days) | Tensile strength, min | 12.5N/mm^2 (1.27kg/mm^2) |
| Variation, max. | ±25% | |
| Elongation at break, min | 200% | |
| Variation, max. | ±25% | |
| Flame retardant PVC | Tensile strength, min | 12.5N/mm^2 (1.27kg/mm^2) |
| Elongation at break, min | 150% | |
| After aging Requiremen (Treatment : Temperature100±2°C, Duration 7days) | Tensile strength, min | 12.5N/mm^2 (1.27kg/mm^2) |
| Variation, max. | ±25% | |
| Elongation at break, min | 150% | |
| Variation, max. | ±25% | |
| Hot set test(Treatment : Temperature200±3°C) | Maximum elongation under load, max. | 175% |
| Maximum permanent elongation after cooling, max. | 15% |